Cookie Img

Lightning current arrester for coaxial line BNC connectors

Lightning current arrester for coaxial line BNC connectors
Lightning current arrester for coaxial line BNC connectors
Product Code : FX-090 B75 T
Product Description

FX-090 B75 T FX-230 B75 T 
Lightning current arrester for coaxial line BNC connectors Designed to protect coaxial lines. It is installed at the boundary of LPZ 0A and LPZ 1 zones at the line entry into the building. It is suitable as the 1st level of surge protection in coordination with the SX type.

Including:

– universal plastic adapter for DIN rail assembling,
– adapter GND 2.
 

Technical data

FX-090 B75 T F/F

FX-230 B75 T F/F

Location SPD

ST 1

ST 1

Maximum operating voltage Uc

70 V DC

180 V DC

Nominal current IL

4 A

4 A

D1 lightning impulse current (10/350 μs) line – SH Iimp

2,5 kA

2,5 kA

D1 lightning impulse current (10/350 μs) SH – PE Iimp

2,5 kA

2,5 kA

C2 nominal discharge current (8/20 μs) line - SH In

10 kA

10 kA

C2 nominal discharge current (8/20 μs) SH - PE In

10 kA

10 kA

C3 voltage protection level line – SH at 1 kV/μs Up

600 V

660 V

C3 voltage protection level SH – PE at 1 kV/μs Up

600 V

660 V

Wave impedance Z

75 Ω

75 Ω

Insertion attenuation

< 0,6 dB

< 0,6 dB

SWR

< 1,2

< 1,2

Bandwidth f

0 – 2,15 GHz

0 – 2,15 GHz

Response time line – SH ta

100 ns

100 ns

Response time SH – PE ta

100 ns

100 ns

Degree of protection

IP 20

IP 20

Range of operating temperatures

– 40 Â°C … + 80 Â°C

– 40 Â°C … + 80 Â°C

Connection input – output

BNC 75

BNC 75

Meets the requirements of standard

EN 61643-21

EN 61643-21

Ordering number

8595090533856

8595090533900

FX-090 B75 T FX-230 B75 T 
Lightning current arrester for coaxial line BNC connectors Designed to protect coaxial lines. It is installed at the boundary of LPZ 0A and LPZ 1 zones at the line entry into the building. It is suitable as the 1st level of surge protection in coordination with the SX type.

Including:

– universal plastic adapter for DIN rail assembling,
– adapter GND 2.
 

Technical data

FX-090 B75 T F/F

FX-230 B75 T F/F

Location SPD

ST 1

ST 1

Maximum operating voltage Uc

70 V DC

180 V DC

Nominal current IL

4 A

4 A

D1 lightning impulse current (10/350 μs) line – SH Iimp

2,5 kA

2,5 kA

D1 lightning impulse current (10/350 μs) SH – PE Iimp

2,5 kA

2,5 kA

C2 nominal discharge current (8/20 μs) line - SH In

10 kA

10 kA

C2 nominal discharge current (8/20 μs) SH - PE In

10 kA

10 kA

C3 voltage protection level line – SH at 1 kV/μs Up

600 V

660 V

C3 voltage protection level SH – PE at 1 kV/μs Up

600 V

660 V

Wave impedance Z

75 Ω

75 Ω

Insertion attenuation

< 0,6 dB

< 0,6 dB

SWR

< 1,2

< 1,2

Bandwidth f

0 – 2,15 GHz

0 – 2,15 GHz

Response time line – SH ta

100 ns

100 ns

Response time SH – PE ta

100 ns

100 ns

Degree of protection

IP 20

IP 20

Range of operating temperatures

– 40 Â°C … + 80 Â°C

– 40 Â°C … + 80 Â°C

Connection input – output

BNC 75

BNC 75

Meets the requirements of standard

EN 61643-21

EN 61643-21

Ordering number

8595090533856

8595090533900

Contact Us

Banarsi Complex, First Floor, Faizabad Road, Opp. Sbi Nishatganj, Lucknow, Uttar Pradesh, 226006, India
Phone :+917042637399