Cookie Img

BDM-24 Combined Class B+C+D Arrester for 2 Wire Telecommunication data line

BDM-24 Combined Class B+C+D Arrester for 2 Wire Telecommunication data line
BDM-24 Combined Class B+C+D Arrester for 2 Wire Telecommunication data line
Product Code : BDM-24
Product Description

Lightning Current Arresters

BDM-06

BDM-12

BDM-24

BDM-48

BDM-230

Lightning current arrester

Combined with coarse and fine surge protection for telecommunication and signalling networks.

Designed to protect 2-wire telecommunication, data and other lines and the communication interface

of M&C, ESS, and EFS control systems, etc. at the boundary of LPZ 0A–LPZ 1 zones and higher. It is

installed directly before the protected equipment. Longitudinal overvoltage (core – earth) and lateral

overvoltage (core – core) are prevented by a threelevel combination of lightning current arrester,

coarse and fine surge protection

Technical data

BDM-06

BDM-12

BDM-24

BDM-48

BDM-230

Location SPD

ST 1+2+3

ST 1+2+3

ST 1+2+3

ST 1+2+3

ST 1+2+3

Nominal voltage Un

6 V DC

12 V DC

24 V DC

48 V DC

230 V DC

Maximum operating voltage Uc

8,1 V DC / 5,7 V AC

14,5 V DC / 10,2 V AC

26,8 V DC / 19 V AC

50,2 V DC / 35,6 V AC

243 V DC / 172 V AC

Nominal current IL

1 A

1 A

1 A

1 A

1 A

D1 total impulse current (10/350 μs) Iimp

5 kA

5 kA

5 kA

5 kA

5 kA

C2 nominal discharge current (8/20 μs) per line In

10 kA

10 kA

10 kA

10 kA

10 kA

C2 voltage protection level line - line at In UP

25 V

40 V

65 V

95 V

800 V

C2 voltage protection level line - PE at In Up

25 V

40 V

65 V

95 V

800 V

C3 voltage protection level line - line at 1 kV/μs Up

14 V

22 V

40 V

75 V

380 V

C3 voltage protection level line - PE at 1 kV/μs Up

14 V

22 V

40 V

75 V

380 V

Series resistance per line R

1 Ω

1 Ω

1 Ω

1 Ω

1 Ω

Threshold frequency line - line fG

4 MHz

11 MHz

17 MHz

24 MHz

53 MHz

Response time line - line ta

1 ns

1 ns

1 ns

1 ns

1 ns

Response time line - PE ta

1 ns

1 ns

1 ns

1 ns

1 ns

Degree of protection

IP 20

IP 20

IP 20

IP 20

IP 20

Range of operating temperatures

– 40 °C … + 80 °C

– 40 °C … + 80 °C

– 40 °C … + 80 °C

– 40 °C … + 80 °C

– 40 °C … + 80 °C

Mounting on

DIN rail 35 mm

DIN rail 35 mm

DIN rail 35 mm

DIN rail 35 mm

DIN rail 35 mm

Cross-section of connected conductors

Solid max

 

Stranded max

 

 ]

 

 ISO: 4 mm2 ; AWG: 11

ISO: 2,5 mm2 ; AWG: 13

 

  

ISO: 4 mm2 ; AWG: 11

ISO: 2,5 mm2 ; AWG: 13

 

 

ISO: 4 mm2 ; AWG: 11

ISO: 2,5 mm2 ; AWG: 13

 

  

ISO: 4 mm2 ; AWG: 11

ISO: 2,5 mm2 ; AWG: 13

 

  

ISO: 4 mm2 ; AWG: 11

ISO: 2,5 mm2 ; AWG: 13

Tightening torque

0,6 Nm

0,6 Nm

0,6 Nm

0,6 Nm

0,6 Nm

Meets the requirements of standard

 

EN 61643-21

 

EN 61643-21

 

EN 61643-21

 

EN 61643-21

 

EN 61643-21

Ordering number

8595090522027

8595090522034

8595090522041

8595090522058

8595090530787

 

Contact Us